Type Gutor PXP 1000 (single phase) Gutor PXP 3000 (three phase)
Ratings 5,10, 15, 20, 30, 40, 50, 60, 80, 100, 120, 140, 160 kVA(Higher ratings upon request)
Operating temperature – 10 to +40 °C (max. 55 °C on request)
Allowable air humidity < 95 % (non condensing)
Noise level 55 – 65 dBA (depending on rating)
Communication protocols Modbus RTU (4-Wire), Modbus TCP, Webpage (HTTP), SNMP, IEC 61850
Altitude above sea level < 1000 m without load de-rating
Input
Rectifier PFC technology (less than 5 % distortion back to line power)
Voltage 3 x 380 / 400 / 415V (other voltages on request)
Voltage tolerance ”+/- 10% for DC in tolerance
-15/+10% for function
Battery circuit
Nominal voltage 400VDC
Applicable batteries Lead Acid, Nickel Cadmium
Output
Voltage 220 / 230 / 240V (others on request) 380 / 400 / 415V (others on request)
Tolerance (static) +/- 1 %
Frequency stability
(free running)
< 0.01 %
Efficiency up to 91% depending on type
Distortion linear load: ≤ 3 % / non-linear load: ≤ 5 %
Overload inverter 200% / 50-100 ms, 150% / 1 min, 125% /10 min
Overload bypass 1000 % / 100 ms, 150 % / 1 min, 125 % / 10 min